Can Watts 009 be installed vertically?

Can Watts 009 be installed vertically?

It can be installed vertically or horizontally (vent elbow required for vertical installation).

What should an RPZ valve be installed with?

The valve must be fitted horizontally with the Tundish below the valve. There must be a clearance of 300-1500mm from the ground, 50mm between the RPZ and any rear wall or cabinet and 150mm above the valve to be accessible for testing.

How does a Watts backflow preventer work?

How Does it Work? A backflow preventer is simplistic yet ingenious in its design. It is comparable to the design of the heart valve in the human heart in that it allows the flow of water through one way and then closes when there is pressure coming back through.

Where to install RP / is-009 series 009 above ground?

In an area where freezing conditions can occur, Series 009 and LF009 should be installed above ground in an insulated enclosure. Series 009 and LF009 must be installed in an acces sible location to facilitate testing and servic ing.

What’s the maximum pressure for a series 009 water line?

Series 009 is ideal for protection of health hazard cross-connections or for containment at the service line entrance. Check with local water authorities for installation requirements. Maximum working pressure is 175 psi (12.06 bar).

What are series 009 reduced pressure zone assemblies?

Series 009 Reduced Pressure Zone Assemblies are designed to protect potable water supplies in accordance with national plumbing codes and water authority requirements.

What are the features of a series 009 Watts?

This series features two in-line, independent check valves, cap- tured springs and replaceable check seats with an intermediate relief valve. Its compact modular design facilitates easy main- tenance and assembly access. Sizes 1竅・/font>4″ 窶・1″ shutoffs have tee handles. Features

In an area where freezing conditions can occur, Series 009 and LF009 should be installed above ground in an insulated enclosure. Series 009 and LF009 must be installed in an acces sible location to facilitate testing and servic ing.

Series 009 is ideal for protection of health hazard cross-connections or for containment at the service line entrance. Check with local water authorities for installation requirements. Maximum working pressure is 175 psi (12.06 bar).

Series 009 Reduced Pressure Zone Assemblies are designed to protect potable water supplies in accordance with national plumbing codes and water authority requirements.

What is the reduced pressure zone in Watts?

Series 009 Reduced Pressure Zone Assemblies prevent the reverse flow of polluted water from entering into the potable water supply due to backsiphonage and or backpressure.